Thermodynamics

Compressed Air Aftercooler Condensation Load & Outlet Humidity Calculator

Calculate condensate mass flow and outlet relative humidity using inlet humidity, discharge pressure, aftercooler temperature, and air mass flow.

Unit-aware inputs Deterministic calculation Engineering interpretation
Calculation workspace

Enter the known values and review the calculated result

Deterministic calculation
01
Parameters

Input parameters

Use consistent values and select the intended engineering units.

Inlet conditions

Compression & aftercooler

Flow

02
Output

Results

Live
Ready to calculate Complete the required inputs and run the calculation.
Engineering Pro Save, document and continue this calculation

Turn this result into a reusable engineering record with saving, PDF export and reporting workflows.

Engineering reference

Method, application and limitations

Review the calculation method, intended application and engineering assumptions before using the result in a design decision.

01
Method

Formula and calculation method

Condensate mass flow formula:

psat(T) = 610.78 · exp((17.27 · (T − 273.15)) / ((T − 273.15) + 237.3))

win = 0.622 · (RHin · psat(Tin)) / (pin − RHin · psat(Tin))

wsat,out = 0.622 · psat(Tcool) / (pout − psat(Tcool))

Δw = win − wsat,out

cond = ṁair · max(0, Δw)

Relative humidity after cooling formula:

RHout = 1, when Δw > 0

RHout = win / wsat,out, when Δw ≤ 0

where:

  • cond — condensate mass flow (kg/s)
  • RHout — relative humidity after cooling (-)
  • psat(T) — saturation vapour pressure at temperature T (Pa)
  • win — inlet humidity ratio (kg/kg)
  • wsat,out — saturated humidity ratio at aftercooler outlet (kg/kg)
  • Δw — humidity ratio difference across the aftercooler (kg/kg)
  • RHin — inlet relative humidity (-)
  • pin — inlet pressure (Pa)
  • pout — discharge pressure (Pa)
  • Tin — inlet temperature (K)
  • Tcool — aftercooler outlet temperature (K)
  • air — air mass flow (kg/s)
02
Application

When to use this calculator

When to use this calculator:

  • Estimate condensate mass flow after cooling compressed air from a defined inlet temperature to a defined aftercooler outlet temperature.
  • Check whether the aftercooler outlet air reaches saturation after compression and cooling.
  • Evaluate condensate load for a compressed-air line using air mass flow and humidity ratio reduction.
  • Compare inlet humidity and outlet saturated humidity ratio to determine whether liquid water is formed.
  • Calculate outlet relative humidity after aftercooling when no condensate is removed.
03
Decision support

How to interpret the result

Condensate mass flow is defined as the amount of liquid water removed per unit time when the inlet humidity ratio exceeds the saturated humidity ratio at the aftercooler outlet.

Outlet relative humidity is defined as saturated air after cooling when condensation occurs, and as the ratio between inlet humidity ratio and outlet saturated humidity ratio when condensation does not occur.

Condensate mass flow depends on air mass flow and humidity ratio reduction. Increasing air mass flow increases condensate mass flow when the humidity ratio reduction is positive. Lowering aftercooler outlet temperature decreases the saturated outlet humidity ratio and can increase condensate mass flow.

  • Safe — returned when the aftercooler outlet temperature is not below the calculated pressure dew point and condensate mass flow is zero.
  • Warning — returned when condensate mass flow is greater than 0.
  • Invalid — returned when the input state violates the validation rules, including zero or negative air mass flow, zero or negative pressure, relative humidity outside 0 to 1, discharge pressure lower than inlet pressure, ineffective cooling, inlet oversaturation, saturation exceeded during compression, or invalid outlet saturation.

The result is used to evaluate whether the aftercooler creates liquid condensate and whether the outlet air leaves the cooler saturated.

04
Worked case

Calculation example

Example:

A user checks condensate formation after cooling compressed air from a hot inlet state to a lower aftercooler outlet temperature.

  • pin — Inlet pressure: 101325 Pa
  • Tin — Inlet temperature: 353.15 K
  • RHin — Relative humidity: 0.50
  • pout — Discharge pressure: 800000 Pa
  • Tcool — Aftercooler outlet temperature: 303.15 K
  • air — Air mass flow: 0.10 kg/s

Result: ṁcond = 0.0187 kg/s and RHout = 1.00.

05
Model boundaries

Assumptions and limitations

  • Saturation vapour pressure is calculated from temperature using the exponential equation implemented in the calculator.
  • Humidity ratio is calculated from vapour pressure, total pressure, and the constant 0.622.
  • Condensate is formed only when inlet humidity ratio is greater than the saturated humidity ratio at the aftercooler outlet.
  • Outlet relative humidity is set to 1 when condensation occurs.
  • Aftercooler outlet temperature must be lower than inlet temperature.
  • Discharge pressure must be greater than or equal to inlet pressure.
06
Questions

Frequently asked questions

How to calculate condensate mass flow?
Condensate mass flow is calculated from air mass flow multiplied by the positive difference between inlet humidity ratio and saturated humidity ratio after cooling. Increasing air mass flow increases condensate mass flow when the humidity ratio difference is positive.
What affects condensate mass flow the most?
Condensate mass flow depends on inlet humidity, inlet temperature, discharge pressure, aftercooler outlet temperature, and air mass flow. Higher inlet humidity increases inlet humidity ratio. Lower aftercooler outlet temperature reduces the saturated humidity ratio after cooling and can increase condensate mass flow.
When is the condensate mass flow formula not valid?
The formula is not valid when air mass flow is zero or negative, pressure is zero or negative, relative humidity is outside 0 to 1, discharge pressure is lower than inlet pressure, aftercooler outlet temperature is not lower than inlet temperature, or the inlet state is already oversaturated.
Can this calculator be used when no condensation occurs?
It can be used when inlet humidity ratio is lower than or equal to the saturated humidity ratio after cooling. In that case, condensate mass flow is zero and outlet relative humidity is calculated from the ratio between inlet humidity ratio and saturated outlet humidity ratio.
Add an engineering note